Model No. | FGPCS-250K/0.4-0.4 | FGPCS-500K/0.4-0.4 |
DC parameters | ||
Max DC input voltage | 900V | |
DC input voltage range | 600~900V | |
Max DC input current | 566A | 1125A |
DC input channels | 1 | |
AC parameters (On-Grid) | ||
Rated AC power | 250kVA | 500kVA |
Max AC power | 275kVA | 550kVA |
Max AC current | 397A | 794A |
Rated AC voltage | 400V | |
AC voltage range | 340~440V | |
Rated frequency range | 50Hz, 45~55Hz | |
AC THDi | <3%(Full load) | |
Power factor | >0.99(Full load) | |
Reactive power adjustment | -1~+1 | |
AC parameters (Off-Grid) | ||
Rated AC voltage | 400V | |
AC voltage range | 340~440V | |
AC THDv | <3%(Linear load) | |
Rated frequency range | 50Hz, 45~55Hz | |
System parameters | ||
Isolation type | Transformer isolated | |
Max efficiency | 96% | 97.3% |
Protection degree | IP20 | |
Running temperature | -30~+60℃(>45℃ derating) | |
Allowable humidity | 0~95% | |
Altitude | 5000m(>2000m derating) | |
Cooling mode | Intelligent forced air cooling | |
Communication | RS485、CAN、Ethernet | |
Dimension(W*H*D) | 1070*2150*870mm | 1470*2150*1070mm |
Weight | 1450kg | 2050kg |