Description |
Value |
Input |
Rated input voltage |
6kV/10kV, -15%~+10% |
Input frequency |
50/60Hz, ±5% |
Input power factor |
≧0.97(Full load) |
System efficiency |
≧98%(Full load) |
Input current harmonic |
≦2%, meet IEC standards of IEEE519~1992 and GB/T14519~93 Quality of electric energy supply-Harmonics in public supply network. 36pulse. |
Output |
Output voltage |
0~6kV/10kV |
Output frequency |
0~120 Hz |
Output current harmonic |
≦2% |
Control performance |
Control mode |
Vector control without PG, V/F control ;Vector control with PG |
Control system |
DSP, FPGA, ARM |
Power system |
UPS, Sustainable 30mins while Power off |
HMI |
10 inch touch screen |
Speed ratio |
1:50 (VF), 1:100 (SVC),1:200(VC) |
Speed control precision |
±1% the maximum speed (VF), ±0.4% the maximum speed (open loop vector);±0.2% the maximum speed (VC) |
Torque response time |
<200ms(open loop vector);<100ms(VC) |
Starting torque |
150% of the rated torque |
Overload protection |
120% of the rated current: 2 mins |
150% of the rated current: 5 s |
200% of the rated current: protect immediately |
ACC/DEC time |
0-3600s, customized |
Signal I/O |
Digital input |
8channels digital input |
Digital output |
8 channels relay output |
Analog input |
3 channels: AI1, AI2: 0~10V/4~20mA; AI3: -10V~10V |
Analog output |
4 channels: AO1, AO2,AO3, AO4: 0~10V/4~20mA |
High speed pulse input |
1 channel: Input range 0~50kHz |
High speed pulse output |
1 channel: Output range 0~50kHz |
Communication method |
Modbus, RS485 interface,Optional: Profibus-DP, Ethernet |
Protection function |
System |
Overcurrent, overvoltage, undervoltage, motor overload, inverter overload, input phase loss, output phase loss |
Overheating, temperature controller fault, communication fault, access fault, uplink communication fault, downlink communication fault, fan overheating |
Unit |
Optical fiber uplink communication fault, optical fiber downlink communication fault, overvoltage, undervoltage, power supply overheating, input phase loss, VCE fault, bypass failure |
Others |
Installation method |
Cabinet mounting |
Protection degree |
IP30 |
Noise degree |
≤75dB |
Feed in and out method |
Bottom in and out; other methods are optional |
Cooling |
Forced-air cooling |
Control power supply |
AC 380V±10% |
MTBF |
50000h |
Temperature of running environment |
-5℃~+50℃ |
Altitude |
Below 1000m; derate 1% for every additional 100m if the sea level is above 1000m. |
Storage |
Keep away from dust, direct sunlight, flammable or corrosive gas, oil, steam and vibration. |
Vibration |
2~9Hz displacement 3mm; 9~20Hz ACC 9.8m/s2; 20~55Hz ACC 2m/s2; 55~200Hz ACC 1m/s2 |